13.2
Parameter levels
Heating circuit HC1
Compact version:
Anl. 1.0.0, 1.0.1, 3.5.0 (= All
HC1
)
Standard version:
Anl. 1.0.0, 1.0.1, 1.1.0, 1.1.1, 1.2.0, 2.0.0, 2.1.0, 2.2.0, 3.5.0,
11.0.0, 11.9.0, 11.9.1 (= All
HC1
)
HC1–
PA1 Parameters
Anl
WE
Setting range
01
Flow gradient; only when
• HC1–CO1–11 = OFF (gradient characteristic)
with HC1–CO1–05 = OFF
with HC1–CO1–05 = ON
All
HC1
1.4
1.0
0.2
0.2
to 3.2
to 1.0
02
Level gradient; only when
• HC1–CO1–11 = OFF (gradient characteristic)
All
HC1
0.0 °C –30.0 to 30.0 °C
03
Flow set point (day); only when
• HC1–CO1–01 = ON (active room sensor)
• HC1–CO1–02 = OFF (fixed set point control)
• HC1–CO1–09 = ON (active flash adaptation)
All
HC1
50.0 °C
5.0 to 130.0 °C
04
Flow set point (night); only when
• HC1–CO1–01 = ON (active room sensor)
• HC1–CO1–02 = OFF (fixed set point control)
• HC1–CO1–09 = ON (active flash adaptation)
All
HC1
30.0 °C
5.0 to 130.0 °C
05
Parameters of four-point characteristic; only when
• HC1–CO1–11 = ON (four-point characteristic)
Outdoor temperature
Point 1
Point 2
Point 3
Point 4
Flow temperature
Point 1
Point 2
Point 3
Point 4
Reduced flow temperature
Point 1
Point 2
Point 3
Point 4
All
HC1
–15.0 °C
–5.0 °C
5.0 °C
15.0 °C
70.0 °C
55.0 °C
40.0 °C
25.0 °C
60.0 °C
40.0 °C
20.0 °C
20.0 °C
–45.0
5.0
5.0
to 50.0 °C
to 150.0 °C
to 150.0 °C
EB 5610 EN
111
Appendix