PA1 Parameters
Anl
WE
Setting range
05
Return flow temperature
Point 1
Point 2
Point 3
Point 4
All
HC1
65.0 °C
65.0 °C
65.0 °C
65.0 °C
5.0 to 90.0 °C
06
Min. flow temperature
All
HC1
20.0 °C
5.0 to 150.0 °C
07
Max. flow temperature
with HC1–CO1–05 = OFF
with HC1–CO1–05 = ON
All
HC1
90.0 °C
50.0 °C
5.0
5.0
to 150.0 °C
to 50.0 °C
08
Night set-back, flow
All
HC1
10.0 K
0.0 to 50.0 K
09
Outdoor temperature for continuous rated opera-
tion (day)
All
HC1
–15.0 °C –35.0 to 5.0 °C
10
Min. flow set point in heating circuit with active
binary demand
All
HC1
40.0 °C
5.0 to 130.0 °C
11
Return flow gradient
All
HC1
1.0
0.2 to 3.2
12
Return flow level
All
HC1
0.0 °C –30.0 to 0.0 °C
13
Return flow temperature foot
All
HC1
65.0 °C
5.0 to 90.0 °C
14
Max. return flow temperature
All
HC1
65.0 °C
5.0 to 90.0 °C
15
Set point boost of pre-control loop
All
HC1
5.0 °C
0.0 to 50.0 °C