Connecting sensors
Cables with a min. cross-section of 0.5 mm² and max. cross-section of 2.5 mm² can be con-
nected to the terminal strips at the back panel of the housing for panel mounting and to the ter-
minal blocks of the base.
Connecting actuators
4
0 to 10 V control output
Connect cables with a min. cross-section of 2 x 0.5 mm².
4
Three-step/on/off control outputs
Route wires with at least 1.5 mm² suitable for damp locations to the terminals of the control-
ler output. The direction of travel needs to be checked at start-up.
Connecting pumps
Route all wires with a minimum cross-section of 1.5 mm² to the controller terminals as shown in
the wiring diagram.
EB 5610 EN
95
Electrical connection