13.4
Technical data
Inputs
Compact version
5
inputs for Pt 1000 temperature sensors, alternatively, binary inputs
for enabling a control circuit, demand processing, flow switch
Standard version
8
inputs for Pt 1000 temperature sensors, alternatively, binary inputs
for enabling a control circuit, demand processing, flow switch
2
0 to 10 V inputs for demand processing, external set point correc-
tion, measured outdoor temperature
Outputs
Compact version
3
relay outputs 230 V AC, 2 A:
1 x control signal output M1 (three-step or on/off)
1 x binary output for a pump
Standard version
2
0 to 10 V outputs for demand, measured outdoor temperature, con-
trol signals
7
relay outputs 230 V AC, 2 A:
1 x control signal output M1 (three-step or on/off)
4 x binary outputs for pumps, fault indication or demand
or
2 x control signal outputs M1 and M2 (three-step or on/off)
3 x binary outputs for pumps, fault indication or demand
Interfaces
1
slot for optional interface boards
Operating voltage
90 to 253 V AC
Power consumption
Compact version:
max. 2.8 VA
Standard version:
max. 4.0 VA
Ambient temperature
0 to 50 °C (operation), –20 °C to 70 °C (storage and transport)
Relative humidity
5 to 95 %, no dew formation
Degree of protection
Without seal for panel mounting:
IP 40 according to IEC 60529
With seal for panel mounting:
IP 41 according to IEC 60529
Class of protection
I according to IEC 61140
Degree of contamination
2 according to IEC 60730
Overvoltage category
III according to IEC 60730
Noise immunity
According to IEC 61000-6-1
Noise emission
According to IEC 61000-6-3
Dimensions W x H x D
Approx. 147 x 96 x 49 mm
Weight
Approx. 0.4 kg
116
EB 5610 EN