2.2
Operation menu
The operating mode is selected in the Operation menu.
The Operation menu cannot be selected when the controller is in manual mode. In this case, you
must first exit the manual mode (
→
Section 4).
The following operating modes are available.
Auto:
The controller uses the day set points within the times-of-use and the night set points
outside the times-of-use (
→
Section 3.1).
If the times-of-use have not been changed, the controller uses the day set points between
06:00 and 22:00 h for control (
→
Section 2.3).
The heating circuit is deactivated accordingly when the heating circuit has an outdoor
sensor and the outdoor temperature exceeds the HC day or night deactivation value
(
→
Section 3.1).
Day:
Regardless of the programmed times-of-use and summer mode, the days set points
are used by the controller (
→
Section 3.1).
The heating circuit
continues
to run when the heating circuit has an outdoor sensor and
the outdoor temperature exceeds the HC day deactivation value (
→
Sections 3.1 and
6.4.1).
Night:
Regardless of the programmed times-of-use, the night set points are used by the
controller (Setting the set points
→
Section 3.1).
The heating circuit is deactivated when the heating circuit has an outdoor sensor and the
outdoor temperature exceeds the HC night deactivation value (
→
Sections 3.1 and 6.4.2).
Stand-by:
Regardless of the programmed times-of-use, the control process is deactivated.
Only the frost protection is activated, if required.