Functions
WE
Configuration
Optimization based on room
temperature
OFF
HC1–CO1–07 = OFF
Optimization based on outdoor
and room temperature
OFF
HC1–CO1–08 = OFF
Flash adaptation
OFF
HC1–CO1–09 = OFF
6.7
Optimization
6.7.1 Optimization based on outdoor temperature
This function requires the use of an outdoor sensor.
The controller activates the heating based on the outdoor temperature before the time-of-use in
day mode. The 'Preheating time' is based on an outdoor temperature of –12 °C. This preheating
time is shortened when the outdoor temperature is higher.
The colder it is outside, the earlier the night set-back finishes to ensure that the selected 'HC1
day set point' is reached as close as possible to the time when the time-of-use starts.
Functions
WE
Configuration
Outdoor temperature measure-
ment
ON
HC1–CO1–02 = ON
Optimization based on outdoor
temperature
OFF
120 min
HC1–CO1–06 = ON
Preheating time / 0 to 360 min
Parameter
WE
Parameter settings
HC1 day set point
Refer to section 3.1
6.7.2 Optimization based on room temperature
This function requires the use of a room sensor. The room in which the room sensor is located
(reference room) should have a similar heating characteristic to the rest of the building. In addi-
tion, this reference room must not have any radiators with thermostatic valves.
Depending on the building characteristics, the controller determines and adapts the required
preheating time (maximum 8 hours) to ensure that the desired 'HC1 day set point' (rated room
temperature) has been reached in the reference room when the time-of-use starts. This temper-
ature is built up in steps of 10 °C. As soon as the 'HC1 day set point' has been reached,
weather-compensated control is activated. Depending on the room sensors, the controller
switches off the heating system up to one hour before the time-of-use ends. The controller
EB 5610 EN
63
Functions of the heating circuit