Parameters
WE
Parameter settings
Outdoor
Point 1
temperature
Point 2
Point 3
Point 4
–15.0 °C
–5.0 °C
5.0 °C
15.0 °C
HC1–PA1–05
/ –45.0 to 50.0 °C
Flow temperature
Point 1
Point 2
Point 3
Point 4
70.0 °C
55.0 °C
40.0 °C
25.0 °C
HC1–PA1–05
/ 5.0 to 150.0 °C
Reduced
Point 1
flow temperature
Point 2
Point 3
Point 4
60.0 °C
40.0 °C
20.0 °C
20.0 °C
HC1–PA1–05
/ 5.0 to 150.0 °C
Return flow
Point 1
temperature
Point 2
Point 3
Point 4
65.0 °C
65.0 °C
65.0 °C
65.0 °C
HC1–PA1–05
/ 5.0 to 90.0 °C
6.2
Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a fixed set point.
Outside the times-of-use, the controller regulates to a reduced flow temperature.
For this function the rated flow temperature is set in 'Day set point' and the reduced flow temper-
ature in 'Night set point'.
Function
WE
Configuration
Outdoor temperature measure-
ment
ON
HC1–CO1–02 = OFF
Parameters
WE
Parameter settings
Min. flow temperature
20.0 °C
HC1–PA1–06 / 5.0 to 150.0 °C
Max. flow temperature
90.0 °C
HC1–PA1–07 / 5.0 to 150.0 °C
HC1 day set point
Refer to section 3.1
HC1 night set point
58
EB 5610 EN
Functions of the heating circuit