Functions
WE
Configuration
Outdoor temperature 0–10 V at
UI1
OFF
–20.0 °C
50.0 °C
HC1–CO1–04 = ON
Lower transmission range value, outdoor tempera-
ture/–30.0 to 100.0 °C
Lower transmission range value, outdoor tempera-
ture/–30.0 to 100.0 °C
6.1.1 Gradient characteristic
Basically, the following rule applies: a decrease in the outdoor temperature causes the flow tem-
perature to increase.
By varying the parameters
Gradient
and
Level
, you can adapt the characteristic to your individ-
ual requirements:
The gradient needs to be increased
if the room temperature
drops when it is cold outside
.
The gradient needs to be decreased
if the room temperature
rises when it is cold outside
.
The level needs to be increased and the gradient decreased
if
the room temperature drops when it is mild outside
.
54
EB 5610 EN
Functions of the heating circuit
t
VL
t
A
[
˚C]
[˚C]
20 0 –20
t
VL
t
A
[˚C]
[˚C]
20 0 –20
t
VL
t
A
[˚C]
[˚C]
20 0 –20