Function
Anl
WE
Comment
Function block parameters
/ Range of values
05
Underfloor
heating
(continued)
25.0 °C
5.0 °C/day
45.0 °C
4 days
0.0 °C/day
0
Function block parameters:
Start temperature / 20.0 to 60.0 °C
Temperature increase / 1.0 to 10.0 °C/day
Max. temperature / 2.0 to 60.0 °C
Max. temperature sustaining time / 1 to 10 days
Temperature reduction / 0.0 to 10.0 °C/day
Start / 0 to 5 (meaning of 0 to 3 on page 59,
4 = drying process successfully completed,
5 = too large system deviation during drying pro-
cess occurred
06
Optimization
based on
outdoor
temperature
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: No optimization
ON: Optimization active; only when
• HC1–CO1–02 = ON
120 min
Function block parameter:
Preheating time / 0 to 360 min
07
Optimization
based on room
temperature
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: No optimization
ON: Optimization active; only when
• HC1–CO1–01 = ON
Function block can only be selected when
• HC1–CO1–06 = OFF and
• HC1–CO1–08 = OFF
08
Optimization
based on out-
door and
room tempe-
rature
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: No optimization
ON: Optimization active; only when
• HC1–CO1–01 = ON
• HC1–CO1–02 = ON
Function block can only be selected when
• HC1–CO1–06 = OFF and
• HC1–CO1–07 = OFF
120 min
Function block parameter:
Preheating time / 0 to 360 min
09
Flash adapta-
tion
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Flash adaptation active; only when
• HC1–CO1–01 = ON
20 min
0.0
Function block parameters:
Cycle time / 0 to 100 min
Gain / 0.0 to 25.0