6
Functions of the heating circuit
Which controller functions are available depends on the selected system number (Anl).
6.1
Weather-compensated control
When weather-compensated control is used, the flow temperature is controlled according to the
outdoor temperature. The heating characteristic in the controller defines the flow temperature
set point as a function of the outdoor temperature (–> Fig. 2). The outdoor temperature required
for weather-compensated control can either be measured at an outdoor sensor or received us-
ing 0 to 10 V at UI1 input.
Functions
WE
Configuration
Outdoor temperature measure-
ment
ON
HC1–CO1–02 = ON
EB 5610 EN
53
Functions of the heating circuit
20
30
0.2
2.4
2.6
2.9
3.2
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.4
0.6
40
50
60
70
80
90
100
110
120
130
t
VL
[
°
C]
–20
[
°
C]
t
A
–16
–12
–8
–4
0
4
8
12
16
20
140
150
–24 –28 –32 –36 –40 –44
Fig. 2 · Gradient characteristics
t
VL
Flow temperature
t
A
Outdoor temperature