DHW-PA4
Range
14-17 Day of week for thermal disinfection
1 to 10
14-18 Start time for thermal disinfection
00:00 to 23:45 h
14-19 Stop time for thermal disinfection
00:00 to 23:45 h
14-20 Disinfection temperature
60.0 to 90.0 °C
14-22 Disinfection temperature boost
0.0 to 5.0 °C
14-21 Disinfection temperature sustaining time
0 to 255 min
14-23 Switching state of control circuit 2 active
0, 1
System-wide HC1
Function block parameters HC1-CO5
Range
04-01 Earliest start date for summer mode
User-definable
04-02 Delay of summer mode active
1 to 3 days
04-03 Latest start date for summer mode
User-definable
04-04 Delay of heating mode active
1 to 3 days
04-05 Outdoor temperature for summer mode
0.0 to 30.0 °C
05-06 Outdoor temperature delay
1 to 6 °C/h
06-06 Outdoor temperature delay
1 to 6 °C/h
07-07 Lower transmission range value, outdoor
temperature
–30.0 to 100.0 °C
07-08 Upper transmission range value, outdoor
temperature
–30.0 to 100.0 °C
09-09 Outdoor temperature for frost protection
–15.0 to 3.0 °C
15-10 Controller switching state active
0, 1
18-11 Lower transmission range value,
demand
0.0 to 130.0 °C
18-12 Upper transmission range value,
demand
0.0 to 130.0 °C
18-13 Demand boost
0.0 to 30.0 °C