DHW heating
Compact version:
Anl. 1.9.0, 1.9.1 (= All
DHW
)
Standard version:
Anl. 1.1.1, 1.2.0, 1.6.0, 1.6.1, 1.6.2, 1.9.0, 1.9.1, 2.0.0, 2.1.0,
2.2.0, 11.0.0, 11.9.0, 11.9.1 (= All
DHW
)
DHW–
CO4–
Function
Anl
WE
Comment
Function block parameters
/ Range of values
01
Storage tank
sensor S7
Not Anl.
1.9.0
1.9.1
11.0.0
11.9.0
11.9.1
OFF
OFF: Storage tank thermostat
ON: Storage tank sensor
Function block can only be selected when
• DHW–CO4–02 = OFF
02
Storage tank
sensor S8
(bottom)
Not Anl.
1.9.0
1.9.1
11.0.0
11.9.0
11.9.1
OFF*
ON**
OFF: Storage tank sensor S8 not active
ON: Storage tank sensor S8 active
Function block can only be selected when
• DHW–CO4–01 = ON
*
Anl. 1.1.0, 1.1.1, 2.0.0, 2.1.0
**
Anl. 1.2.0, 1.6.0, 1.6.1, 1.6.2, 2.2.0
03
Return flow
temperature
measurement
Not Anl.
1.1.0
1.1.1
1.2.0
2.0.0
2.1.0
2.2.0
OFF*
ON**
OFF: Return flow sensor not active
ON: Return flow temperature measurement and limita-
tion active
1.0
Function block parameter:
Limiting factor / 0.1 to 10.0
*
Anl. 1.6.2
** Anl. 1.6.0, 1.6.1, 1.9.0, 1.9.1, 11.0.0, 11.9.0, 11.9.1
04
Flow rate
detection
Only Anl.
1.9.0,
11.9.0,
11.9.1
OFF
OFF: Function inactive
ON: Flow rate detection active
05
Flow sensor
DHW
Not Anl.
1.9.0
1.9.1
2.0.0
2.1.0
11.0.0
11.9.0
OFF
OFF: Flow sensor DHW not active
ON: Flow sensor for measuring the storage tank
charging temperature active
104
EB 5610 EN
Appendix