6.8.1 Flash adaptation without outdoor sensor (based on room
temperature)
The flow temperature control starts with 'Flow set point (day)' in day mode or with 'Flow set
point (night)' in night mode as no set points calculated using characteristics exist without an out-
door sensor. The 'Cycle time' determines the intervals at which the flow temperature set point is
corrected by 1 °C. The heating is then always switched off as soon as the room temperature ex-
ceeds the 'HC1 day set point' or 'HC1 night set point' by 2.0 °C. Heating first starts again when
the room has cooled off and the room temperature is 1 °C above the set point. 'Gain' set to a
value other than 0 causes a direct increase/decrease in flow temperature set point when a sud-
den deviation in room temperature arises. We recommend setting 'Gain' to 10.0.
Functions
WE
Configuration
Room temperature measurement OFF
HC1–CO1–01 = ON
Outdoor temperature measure-
ment
ON
HC1–CO1–02 = OFF
Flash adaptation
OFF
20 min
0.0
HC1–CO1–09 = ON
Cycle time / 0 to 100 min
Gain / 0.0 to 25.0
Parameters
WE
Parameter settings
Flow set point (day)
50.0 °C
HC1–PA1–03 / 5.0 to 130.0 °C
Flow set point (night)
30.0 °C
HC1–PA1–04 / 5.0 to 130.0 °C
HC1 day set point
Refer to section 3.1
HC1 night set point
6.9
Adaptation
The controller is capable of automatically adapting the heating characteristic to the building
characteristics, provided a gradient characteristic has been set (HC1–CO1–11 = OFF). The ref-
erence room, where the room sensor is located, represents the entire building and is monitored
to ensure that the room set point ('HC1 day set point') is maintained. When the measured mean
room temperature in day mode deviates from the adjusted set point, the heating characteristic is
modified accordingly for the next time-of-use.