HC1–
CO5–
Function
Anl
WE
Comment
Function block parameters
/ Range of values
08
Summer/winter
time switchover
All
ON
OFF: Function inactive
ON: Automatic summer/winter time switchover
09
Highest priority
for frost protec-
tion
All
OFF*
ON**
OFF: Restricted frost protection
ON: Highest priority for frost protection
3.0 °C
Function block parameters:
Outdoor temperature for frost protection / –15.0 to
3.0 °C
*
Anl. 1.6.0, 1.6.1, 1.6.2, 1.9.0, 1.9.1
** Anl. 1.0.0, 1.0.1, 1.1.0, 1.1.1, 1.2.0, 2.0.0, 2.1.0,
2.2.0, 11.0.0, 11.9.0, 11.9.1
10
to
14
Reserved
15
Unlock con-
troller at S5
All
OFF
OFF: Function inactive
ON: Unlock controller at S5 depending on switching
state
1
Function block parameters:
Controller switching state active / 0, 1
16
Return flow lim-
itation by PI
algorithm
OFF
OFF: Return flow limitation by P algorithm
ON: Return flow limitation by PI algorithm
17
Fault indication
output
All
OFF
OFF: Function inactive
ON: Error message
18
Demand
0–10 V at
UO1
All
OFF
0.0 °C
120.0 °C
0.0 °C
OFF: Function inactive
ON: Demand at UO1 active
Function block parameters:
Lower transmission range value, demand / 0.0 to
130.0 °C
Upper transmission range value, demand / 0.0 to
130.0 °C
Demand boost / 0.0 to 30.0 °C
19
Temperature
monitoring
All
OFF
OFF: Function inactive
ON: Temperature monitoring at VS, RS and RüS
EB 5610 EN
109
Appendix