HC1–
CO1–
Function
Anl
WE
Comment
Function block parameters
/ Range of values
10
Adaptation
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Adaptation active; only when
• HC1–CO1–01 = ON and
• HC1–CO1–02 = ON and
• HC1–CO1-11 = OFF
11
Four-point
characteristic
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Gradient characteristic
ON: Four-point characteristic; only when
• HC1–CO1–10 = OFF
12
Three-step
control
Not Anl.
1.9.0
1.9.1
ON
OFF: On/off control
ON: Three-step control/continuous control
5.0 °C
120 s
120 s
2.0
120 s
0 s
45 s
Function block parameters:
On/off control
Hysteresis / 2.0 to 10.0 °C
Min. ON time / 0 to 600 s
Min. OUT time / 0 to 600 s
Three-step control/continuous control
Gain KP / 0.1 to 50.0
Reset time TN / 0 to 999 s
Derivative-action time TV / 0 to 999 s;
Do not change this value!
Valve transit time TY-OPEN / 10 to 240 s
13
OPEN signal
damping
Not Anl.
1.9.0
1.9.1
OFF
OFF: Function inactive
ON: Damping active
2.0 °C
Function block parameter:
Max. system deviation / 2.0 to 10.0 °C
14
Unlock control
loop 1 at S5
All
HC1
OFF
1
OFF: Function inactive
ON: Unlock control loop 1 at S5 depending on the
switching state
Function block parameter:
Control loop 1 switching state active / 0, 1
15
Set point cor-
rection using
0–10 V
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Set point correction active
16
Demand pro-
cessing 0-10 V
at UI1
Not Anl.
1.9.0
1.9.1
OFF
OFF: Function inactive
ON: Demand processing at UI1 active
102
EB 5610 EN
Appendix