System-wide functions HC1
Compact version:
Anl. 1.0.0, 1.0.1, 1.9.0, 1.9.1, 3.5.0
Standard version:
All systems
HC1–
CO5–
Function
Anl
WE
Comment
Function block parameters
/ Range of values
01
03
Reserved
04
Summer mode
Not Anl.
1.6.0
1.6.1
1.6.2
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Summer mode
01.06
2 days
30.09
1 day
18.0 °C
Function block parameters:
Earliest start date for summer mode / User-definable
Delay of summer mode active / 1 to 3 days
Latest stop date for summer mode / User-definable
Delay of heating mode active / 1 to 3 days
Outdoor temperature for summer mode / 0.0 to 30.0 °C
05
Delay de-
creasing
outdoor tem-
perature
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Control when delay decreasing outdoor tempera-
ture
3 °C/h
Function block parameter:
Outdoor temperature delay / 1 to 6 °C/h
Note:
The setting of this function block parameter
changes the function parameter in HC1–CO5–06!
06
Delay
increasing out-
door tempera-
ture
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Control when delay increasing outdoor tempera-
ture
3 °C/h
Function block parameter:
Outdoor temperature delay / 1 to 6 °C/h
Note:
The setting of this function block parameter
changes the function parameter in HC1–CO5–05!
07
Outdoor tem-
perature
0–10 V at
UO1
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Outdoor temperature forwarded at analog output
UO1
–20.0 °C
50.0 °C
Function block parameters:
Lower transmission range value, outdoor tempera-
ture / –30.0 to 100.0 °C
Upper transmission range value, outdoor tempera-
ture / –30.0 to 100.0 °C
108
EB 5610 EN
Appendix