HC1-PA1
Range
13-21 Max. system deviation
2.0 to 10.0 °C
14-22 Control loop 1 switching state active
0, 1
17-23 Demand switching state active
0, 1
DHW heating
DHW-PA4
Range
01
Min. adjustable DHW set point
5.0 to 90.0 °C
02
Max. adjustable DHW set point
5.0 to 90.0 °C
03
Hysteresis
1.0 to 30.0 °C
04
Charging temperature boost
20.0 to 50.0 °C
05
Max. charging temperature
20.0 to 130.0 °C
06
Lag time of storage tank charging pump
0 to 600 s
07
Max. return flow temperature
20.0 to 90.0 °C
Function block parameters DHW-CO4
03-01 Limiting factor
0.1 to 10.0
06-03 Delay of cancelation due to system deviation
0 to 10 min
06-04 Min. flow set point in heating circuit for
parallel pump operation
20.0 to 90.0 °C
08-05 Delay of reverse control active
0 to 10 min
08-06 Correction factor
0.1 to 1.0
09-07 Delay of set-back operation active
0 to 10 min
12-13 Hysteresis
2.0 to 10.0 °C
12-14 Min. ON time
0 to 600 s
12-15 Min. OFF time
0 to 600 s
12-08 Gain KP
0.1 to 50.0
12-09 Reset time TN
0 to 999 s
12-10 Derivative-action time TV
0 to 999 s
12-11 Valve transit time TY-OPEN
10 to 240 s
13-16 Max. system deviation
2.0 to 10.0 °C
120
EB 5610 EN
Appendix