8.10.2 Processing an external demand with a 0 to 10 V signal
The controller (= primary controller) can process analog external demands. The 0 to 10 V signal
is interpreted as a flow temperature demand of 0.0 to 120.0 °C, i.e. the flow temperature de-
mand is 12 °C/V.
The set point of the downstream secondary controller is read at the analog input UI1 and com-
pared with the controller's own flow temperature set point. The higher of the flow temperature
set points plus 'Set point boost of pre-control loop' is used by the controller to regulate the flow
temperature. The 'Set point boost of pre-control loop' parameter improves the control behavior
of the downstream heating circuit instruments and compensates for any loss in capacity.
Functions
WE
Configuration
Demand processing 0-10 V at UI1
OFF
HC1–CO1–16 = ON
Primary controller: Parameter
WE
Parameter settings
Set point boost of pre-control loop
5 °C
HC1–PA1–15 / 0.0 to 50.0 °C
8.11
Demand requested with a 0 to 10 V signal
The controller can request its maximum flow set point (with boost, if required) by issuing a 0 to
10 V signal. The output UO1 is used.
Function
WE
Configuration
Demand 0–10 V at UO1
OFF
0.0 °C
120.0 °C
30.0 °C
HC5–CO5–18 = ON
Lower transmission range value, demand /
0.0 to 130.0 °C
Upper transmission range value, demand /
0.0 to 130.0 °C
Demand boost / 0.0 to 30.0 °C
8.12
Forwarding the measured outdoor temperature
The controller can make the measured outdoor temperature available to a downstream control-
ler. The 'Lower transmission range value, outdoor temperature' and the 'Upper transmission
range value, outdoor temperature' is assigned to a 0 to 10 V signal. The downstream controller
uses the outdoor temperature to determine the flow rate temperature.
EB 5610 EN
87
System-wide functions
Summary of Contents for trovis 5600
Page 22: ...22 EB 5610 EN Setup settings B C D A A...
Page 124: ...124 EB 5610 EN...
Page 125: ...EB 5610 EN 125...
Page 126: ...126 EB 5610 EN Key number 1732...