Functions
WE
Configuration
Return flow temperature measurement
1.0
HC1–CO1–03 = ON
Limiting factor / 0.1 to 10.0
Return flow temperature measurement
1.0
DHW–CO4–03 = ON
Limiting factor / 0.1 to 10.0
Control algorithm:
Return flow limitation by PI algorithm
OFF
HC1–CO5–16 = OFF: P algorithm
HC1–CO5–16 = ON: PI algorithm
Parameters
WE
Parameter settings
Return flow gradient
1.0
HC1–PA1–11 / 0.2 to 3.2
Return flow level
0.0 °C
HC1–PA1–12 / –30.0 to 0.0 °C
Return flow temperature foot
65.0 °C
HC1–PA1–13 / 5.0 to 90.0 °C
Max. return flow temperature
65.0 °C
HC1–PA1–14 / 5.0 to 90.0 °C
Return flow temperature, points 1 to 4
65.0 °C
HC1–PA1–05 / 5.0 to 90.0 °C
Max. return flow temperature
65.0 °C
DHW–PA4–07 / 20.0 to 90.0 °C
8.5
Condensate accumulation control
Activate the
OPEN signal damping
function to start up condensate accumulation plants, in par-
ticular to avoid problematic excess temperatures. The controller response to set point deviations
which cause the primary valve to open is attenuated. The controller response to set point devia-
tions which cause the control valve to close remains unaffected.
Note:
The condensate accumulation control function can only be activated when three-step con-
trol has been configured for the control circuit (refer to section 8.6).
Functions
WE
Configuration
Three-step control
ON
HC1–CO1–12 = ON
OPEN signal damping
OFF
2.0 °C
HC1–CO1–13 = ON
Max. system deviation / 2.0 to 10.0 °C
Three-step control
ON
DHW–CO4–12 = ON
OPEN signal damping
OFF
2.0 °C
DHW–CO4–13 = ON
Max. system deviation / 2.0 to 10.0 °C
82
EB 5610 EN
System-wide functions