Manual mode
All outputs can be set in the manual mode:
4
M
(control valve): control output in percent
4
UP
(heating pump): switching pump on and off (ON/OFF)
4
SLP
(storage tank charging pump): switching pump on and off (ON/OFF)
4
ZP
(circulation pump): switching pump on and off (ON/OFF)
NOTICE
The heating is not monitored for frost protection in manual mode.
The following instructions describe the procedure starting from the start screen (see page 9).
Open the Manual menu.
The outputs of the control circuit (specified in the sec-
ond row) are shown.
Select the output you want to control manually.
Set output.
The output immediately switches from automatic mode
to the manual mode
.
Standard version
and heating systems with two control
circuits:
Select the manual mode for DHW heating, if
required.
Set the other outputs in the same manner as described
above.
EB 5610 EN
33
Manual mode