58
Rockwell Automation Publication 2093-AP001A-EN-P - May 2014
Appendix C
Specifications
Power Dissipation
Specifications
Kinetix 2000 Servo Drive Power Dissipation Specifications
Use the following table to size an enclosure and calculate required ventilation for
a Kinetix 2000 servo drive system.
Kinetix 5500 Servo Drive Power Dissipation Specifications
Use this table to size an enclosure and calculate required ventilation for a
Kinetix 5500 drive system.
Kinetix 2000 Servo Drive Modules
Usage as a Percentage of Rated Power Output (Watts)
20%
40%
60%
80%
100%
Converter (IAM)
(1)
2093-AC05-MP1
Three-phase
7.0 10.5 14.0 17.4 20.9
2093-AC05-MP2
2093-AC09-MP5
2093-AC05-MP1
Single-phase
5.8 8.0 10.3 12.6 14.8
2093-AC05-MP2
2093-AC09-MP5
Inverter (IAM and AM)
(1)
(1) Internal shunt power is not included in the calculations and must be added based on utilization.
2093-AC05-MP1
and
2093-AMP1
31.6 33.6 35.6 37.6 39.6
2093-AC05-MP2
and
2093-AMP2
33.0 36.4 39.8 43.3 46.8
2093-AC05-MP5
and
2093-AMP5
36.2 42.9 49.8 56.8 63.9
2093-AM01
38. 3
46.7
55. 3
64. 1
73. 1
2093-AM02
44. 3
55.6
67. 3
79.2
91.4
Shunt module (SM)
2093-ASP06
35.8 45.8 55.8 65.8 75.8
Power Rail
2093-PRS
xx
0 0 0 0 0
Connector Kit
2093-K2CK-D15M
0 0 0 0 0
Kinetix 5500
Servo Drive
Cat. No.
Usage as % of Rated Power Output (Watts)
20%
40%
60%
80%
100%
2198-H003-ERSx
12 25 37 50 62
2198-H008-ERSx
2198-H015-ERSx
40 80 120 160 200
2198-H025-ERSx
2198-H040-ERSx
2198-H070-ERSx
64 128 192 256 320
Summary of Contents for Allen-Bradley Kinetix 2000
Page 1: ...Kinetix 2000 Multi axis Servo Drives to Kinetix 5500 Servo Drives Migration Guide...
Page 6: ...6 Rockwell Automation Publication 2093 AP001A EN P May 2014 Table of Contents...
Page 12: ...12 Rockwell Automation Publication 2093 AP001A EN P May 2014 Preface Notes...
Page 62: ...62 Rockwell Automation Publication 2093 AP001A EN P May 2014 Appendix C Specifications Notes...
Page 75: ......