326
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 8
Metering and Diagnostics
L3 Percent FLA
L3 Percent FLA (Parameter 49) reports the L3 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L3 Percent FLA = L3 Current / Full Load Amps
Table 396 - L3 Percent FLA (Parameter 49)
Average Percent FLA
Average Percent FLA (Parameter 50) reports the average current in comparison
to the active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
Average Percent FLA = Average Current / Full Load Amps
Table 397 - Average Percent FLA (Parameter 50)
Ground Fault Current
Ground Fault Current (Parameter 51) reports the ground fault current measured
by the internal core balanced current transformer of the E300 Electronic
Overload Relay Sensing Module or external core balanced current transformer.
Table 398 - Ground Fault Current (Parameter 51)
Default Value
0.0
Minimum Value
0.0
Maximum Value
1000.00
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
%
Default Value
0.0
Minimum Value
0.0
Maximum Value
1000.00
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
%
Default Value
0.0
Minimum Value
0.0
Maximum Value
99.99
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
100
Units
Amps
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......