Chapter 6
Protective Trip and Warning Functions
Table 217 - Line Loss Inhibit Time (Parameter 285)
L1 Line Loss Trip
The E300 Electronic Overload Relay trips with a L1 Line Loss indication if:
•
No trip currently exists
•
L1 Over Current Trip is enabled
•
L1 Line Loss is activated via the appropriately programmed digital input
(see Input Assignments, Parameters 196…201, in
•
Line Loss Inhibit Timer has expired
•
L1 Percent FLA (Parameter 47) is
•
equal to 0% for a time period greater than the L1 Line Loss Trip Delay.
If the E300 Electronic Overload Relay trips on a L1 Line Loss, the:
•
TRIP/WARN LED status indicator flashes a red 14-short blink pattern
•
Bit 13 in Current Trip Status (Parameter 4) sets to 1
•
Bit 0 in Device Status 0 (Parameter 20) sets to 1
•
Any relay outputs configured as a Trip Relay open
•
Any relay outputs configured as a Control Relay open
•
Any relay outputs configured as a Trip Alarm close
•
Any relay outputs configured as a Normal Relay are placed in their
Protection Fault state (if so programmed)
Default Value
10
Minimum Value
0
Maximum Value
250
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
Seconds
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......