162
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 6
Protective Trip and Warning Functions
L1 Under Current Trip Level
L1 Under Current Trip Level (Parameter 267) allows you to define the current at
which the E300 Electronic Overload Relay trips on a L1 Under Current. It is
user-adjustable from 10…100% of the FLA Setting (Parameter 171).
Table 199 - L1 Under Current Trip Level (Parameter 267)
L1 Under Current Warning
The E300 Electronic Overload Relay indicates an L1 Under Current warning if:
•
No warning currently exists
•
L1 Under Current Warning is enabled
•
Current is present
•
The Under Current Inhibit Timer has expired
•
L1 Percent FLA (Parameter 47) is less than the L1 Under Current
Warning Level
When the L1 Under Current Warning conditions are satisfied, the:
•
TRIP/WARN LED flashes a yellow 8-short blink pattern
•
Bit 7 in Current Warning Status (Parameter 10) sets to 1
•
Bit 1 in Device Status 0 (Parameter 20) sets to 1
•
Any relay outputs configured as a Warning Alarm close
L1 Under Current Warning Level
L1 Under Current Warning Level (Parameter 268) allows you to define the
current at which the E300 Electronic Overload Relay indicates a L1 Under
Default Value
35
Minimum Value
10
Maximum Value
100
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
%FLA
IMPORTANT
The Under Current Inhibit Timer starts after the maximum phase of load
current transitions from 0 A to 30% of the minimum FLA setting of the device.
The E300 Electronic Overload Relay does not begin monitoring for an
undercurrent condition until the Under Current Inhibit Time expires.
IMPORTANT
For any given application, the practical limit of the L1 Under Current Trip Level
(Parameter 267) is dependent on the FLA Setting and the lower limit of the
E300 Electronic Overload Relay’s current measurement capability
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......