Rockwell Automation Publication 193-UM015D-EN-P - February 2015
85
System Operation and Configuration
Chapter 4
Table 52 - Emergency Start (Parameter 216)
Configure one of the Ptxx Input Assignments (Parameters 196…201) to
Emergency Start and activate the corresponding digital input.
Table 53 - Emergency Start Input PTXX Assignment (Parameters 196…201)
You can also use a network command to activate the Emergency Start feature. For
the EtherNet/IP communications module, you would set the Emergency Start
bit to 1 in Output Assembly 144. See
for more information on EtherNet/IP communications.
When the Emergency Start feature is active, the following actions occur in the
E300 Electronic Overload Relay:
•
Protection trips are ignored
•
Output relays configured as Trip Relays are put into closed state
•
Normal operation resumes with any Normal or Control Relay assigned
output relay
•
The Emergency Start Active bit is set to 1 in Device Status 0
(Parameter 20) bit 6
Value
Description
0
Disable
1
Enable
Value
Assignment
Description
0
Normal
Function as a digital input
1
Trip Reset
Reset the E300 when it is in a tripped state
2
Remote Trip
Force the E300 to go into a tripped state
3
Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current-based
protection algorithms
4
Force Snapshot
Force the E300 to update its Snapshot log
5
Emergency Start
Issue an Emergency Start command
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......