Rockwell Automation Publication 193-UM015D-EN-P - February 2015
287
Protective Trip and Warning Functions
Chapter 6
Analog Module 4 – Channel 01 Over Level Trip Delay
Analog Module 4 – Channel 01 Over Level Trip Delay (Parameter 545) allows
you to define the time period an Analog Module 4 – Channel 01 Over Level
condition must be present before a trip occurs. It is adjustable from 0.1…25.0
seconds.
Table 346 - Analog Module 4 – Channel 01 Over Level Trip Delay (Parameter 545)
Analog Module 4 – Channel 01 Trip Level
Analog Module 4 – Channel 01 Trip Level (Parameter 546) allows you to define
the magnitude of the analog signal in which the E300 Electronic Overload Relay
trips on an Analog Module 4 – Channel 01 Over Level trip. It is user-adjustable
from -32768…+32767.
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
•
Output PT00 Protection Fault Action (Parameter 304)
•
Output PT00 Protection Fault Value (Parameter 305)
•
Output PT01 Protection Fault Action (Parameter 310)
•
Output PT01 Protection Fault Value (Parameter 311)
•
Output PT02 Protection Fault Action (Parameter 316)
•
Output PT02 Protection Fault Value (Parameter 317)
•
Output Digital Module 1 Protection Fault Action (Parameter 322)
•
Output Digital Module 1 Protection Fault Value (Parameter 323)
•
Output Digital Module 2 Protection Fault Action (Parameter 328)
•
Output Digital Module 2 Protection Fault Value (Parameter 329)
•
Output Digital Module 3 Protection Fault Action (Parameter 334)
•
Output Digital Module 3 Protection Fault Value (Parameter 335)
•
Output Digital Module 4 Protection Fault Action (Parameter 340)
•
Output Digital Module 4 Protection Fault Value (Parameter 342)
Default Value
1.0
Minimum Value
0.1
Maximum Value
25.0
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
10
Units
Seconds
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......