Rockwell Automation Publication 193-UM015D-EN-P - February 2015
471
Parameter List
Appendix
B
Trip/Warn History
(continued)
148
WarnHistoryMaskC
C.History.PTCWarningEn
C.History.ModuleMismatchWarningEn
C.History.ExpansionBusWarningEn
C.History.NumberOfStartsWarningEn
C.History.OperatingHoursWarningEn
Warning History
Mask for Control-
based Warnings
UINT
2
1
Bit0= Reserved
Bit1= PTCWarning
Bit2= DLXWarning
Bit3= Reserved
Bit4= Reserved
Bit5= Reserved
Bit6= Reserved
Bit7= ConfigWarning
Bit8= OptionMatchWarn
Bit9= DLXFBTimeoutWarn
Bit10= ExpansionBusWarn
Bit11= PMNumberOfStarts
Bit12= PMOperatingHours
0x1FFF
149
WarnHistoryMaskA
C.History.Analog1Ch00WarningEn
C.History.Analog1Ch01WarningEn
C.History.Analog1Ch02WarningEn
C.History.Analog2Ch00WarningEn
C.History.Analog2Ch01WarningEn
C.History.Analog2Ch02WarningEn
C.History.Analog3Ch00WarningEn
C.History.Analog3Ch01WarningEn
C.History.Analog3Ch02WarningEn
C.History.Analog4Ch00WarningEn
C.History.Analog4Ch01WarningEn
C.History.Analog4Ch02WarningEn
Warning History
Mask for Analog
Input Based
Warnings
UINT
2
1
Bit0= InAnMod1Ch00Warn
Bit1= InAnMod1Ch01Warn
Bit2= InAnMod1Ch02Warn
Bit3= InAnMod2Ch00Warn
Bit4= InAnMod2Ch01Warn
Bit5= InAnMod2Ch02Warn
Bit6= InAnMod3Ch00Warn
Bit7= InAnMod3Ch01Warn
Bit8= InAnMod3Ch02Warn
Bit9= InAnMod4Ch00Warn
Bit10= InAnMod4Ch01Warn
Bit11= InAnMod4Ch02Warn
0xFFF
150
Reserved
Trip Snapshot
151
TSL1Current
Snapshot of the
actual L1 Phase
Current at trip
DINT
4
100
0
2000000000
0
Amps
152
TSL2Current
Snapshot of the
actual L2 Phase
Current at trip
DINT
4
100
0
2000000000
0
Amps
153
TSL3Current
Snapshot of the
actual L3 Phase
Current at trip
DINT
4
100
0
2000000000
0
Amps
154
TSThermUtilized
Snapshot of %
Thermal Capacity
Used at trip
UINT
2
1
0
100
0
%
155
TSGFCurrent
Snapshot of the
Ground Fault
Current at trip
INT
2
100
0
2540
0
Amps
156
TSL1toL2Voltage
Snapshot of 3
Phase RMS Voltage
Line-Line at trip
UINT
2
10
0
65535
0
Volt
157
TSL2toL3Voltage
Snapshot of 3
Phase RMS Voltage
Line-Line at trip
UINT
2
10
0
65535
0
Volt
158
TSL3toL1Voltage
Snapshot of 3
Phase RMS Voltage
Line-Line at trip
UINT
2
10
0
65535
0
Volt
159
TSTotalRealPwr
Snapshot of Total
Real Power at trip
DINT
4
1000
-2000000000 2000000000
0
kW
160
TSTotalkVAR
Snapshot of Total
Reactive Power at
trip
DINT
4
1000
-2000000000 2000000000
0
kVAR
161
TSTotalkVA
Snapshot of Total
Apparent Power at
trip
DINT
4
1000
0
2000000000
0
kVA
162
TSTotalPF
Snapshot of Total
True Power Factor
(PF) at trip
INT
2
10
-1000
1000
0
%
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......