Rockwell Automation Publication 193-UM015D-EN-P - February 2015
127
Operating Modes
Chapter 5
Timing Diagram
Figure 45 - Timing Diagram
Monitor (Custom)
The E300 Electronic Overload Relay’s Monitor (Custom) Operating Mode
allows you to use the E300 Electronic Overload Relay as a monitoring device. No
configuration rules apply in this operating mode if the motor protection features
are disabled.
Rules
1.
If any protection trips are enabled (excluding Configuration, NVS, and
Hardware Fault trip), then set any of the Output Ptxx Assignments
(Parameters 202…204) to the appropriate value of Trip Relay, Control
Relay, Monitor Lx Trip Relay, or Monitor Lx Control Relay.
Wiring Diagram
Not Applicable
Timing Diagram
Not Applicable
Trip Relay
or
Control Relay
Trip Reset
Device
Status0.Trip
Present