208
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 6
Protective Trip and Warning Functions
•
Any relay outputs configured as a Trip Relay open
•
Any relay outputs configured as a Control Relay open
•
Any relay outputs configured as a Trip Alarm close
•
Any relay outputs configured as a Normal Relay are placed in their
Protection Fault state (if so programmed)
Under kW Trip Delay
Under kW Trip Delay (Parameter 379) allows you to define the time period an
under real power (kW) condition must be present before a trip occurs. It is
adjustable from 0.1…25.0 seconds.
Table 254 - Under kW Trip Delay (Parameter 379)
Under kW Trip Level
Under kW Trip Level (Parameter 380) allows you to define the real power (kW)
at which the E300 Electronic Overload Relay trips on an under real power (kW).
It is user-adjustable from 0…2,000,000 kW.
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
•
Output PT00 Protection Fault Action (Parameter 304)
•
Output PT00 Protection Fault Value (Parameter 305)
•
Output PT01 Protection Fault Action (Parameter 310)
•
Output PT01 Protection Fault Value (Parameter 311)
•
Output PT02 Protection Fault Action (Parameter 316)
•
Output PT02 Protection Fault Value (Parameter 317)
•
Output Digital Module 1 Protection Fault Action (Parameter 322)
•
Output Digital Module 1 Protection Fault Value (Parameter 323)
•
Output Digital Module 2 Protection Fault Action (Parameter 328)
•
Output Digital Module 2 Protection Fault Value (Parameter 329)
•
Output Digital Module 3 Protection Fault Action (Parameter 334)
•
Output Digital Module 3 Protection Fault Value (Parameter 335)
•
Output Digital Module 4 Protection Fault Action (Parameter 340)
•
Output Digital Module 4 Protection Fault Value (Parameter 342)
Default Value
1.0
Minimum Value
0.1
Maximum Value
25.0
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
10
Units
Seconds
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......