252
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 6
Protective Trip and Warning Functions
Starts Interval
Starts Interval (Parameter 206) is the time that you must wait between starts.
This value is adjustable from 0…3600 seconds.
Table 305 - Starts Interval (Parameter 206)
Starts Available
Starts Available (Parameter 30) reports the number of starts currently available
based on the blocked start settings and the actual motor starting events.
Table 306 - Starts Available (Parameter 30)
Time to Start
Time to Start (Parameter 31) reports the amount of the time remaining until a
new start can be issued. If the Time to Start time has elapsed, this parameter
reports zero until the next Blocked Start trip occurs.
Table 307 - Time to Start (Parameter 31)
Default Value
600
Minimum Value
0
Maximum Value
3600
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
1
Units
Seconds
Default Value
0
Minimum Value
0
Maximum Value
120
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
Default Value
0
Minimum Value
0
Maximum Value
3600
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
1
Units
Seconds
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......