Chapter 8
Metering and Diagnostics
Table 417 - L1 Reactive Power (Parameter 68)
L2 Reactive Power
L2 Reactive Power (Parameter 69) reports the reactive power for line 2 in kVAR
or MVAR depending on the configuration value for Power Scale (Parameter
377). When Voltage Mode (Parameter 352) is set to any
Delta
base setting, L2
Reactive Power is set to 0.
Table 418 - L2 Reactive Power (Parameter 69)
L3 Reactive Power
L3 Reactive Power (Parameter 70) reports the reactive power for line 3 in kVAR
or MVAR depending on the configuration value for Power Scale (Parameter
377). When Voltage Mode (Parameter 352) is set to any
Delta
base setting, L3
Reactive Power is set to 0. When Single or Three Phase (Parameter 176) is set to
Single Phase
, L3 Reactive Power is set to 0.
Table 419 - L3 Reactive Power (Parameter 70)
Total Reactive Power
Total Reactive Power (Parameter 71) reports the total Reactive power of the
monitored power conductors in kVAR or MVAR depending on the
Default Value
0.000
Minimum Value
-2000000.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVAR or MVAR
Default Value
0.000
Minimum Value
-2000000.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVAR or MVAR
Default Value
0.000
Minimum Value
-2000000.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVAR or MVAR
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......