EtherNet/IP Information
Appendix C
The table below lists Fault Codes, Fault Text, and Fault Help Strings.
Table 585 - Fault Codes, Fault Text, and Fault Help Strings
Fault Code
Fault Text
Help Text
0
No Fault
No Fault Conditions Detected
1
OverloadTrip
Motor current overload condition
2
PhaseLossTrip
Phase current Loss detected in one of the motor phases
3
GroundFaultTrip
Power conductor or motor winding is shorting to ground
4
StallTrip
Motor has not reached full speed by the end of Stall Enable Time
5
JamTrip
Motor current has exceed the programmed jam trip level
6
UnderloadTrip
Motor current has fallen below normal operating levels
7
Current Imbal
Phase to phase current imbalance detected
8
L1UnderCurrTrip
L1Current was below L1 Undercurrent Level longer than Trip Delay
9
L2UnderCurrTrip
L2Current was below L2 Undercurrent Level longer than Trip Delay
10
L3UnderCurrTrip
L3Current was below L3 Undercurrent Level longer than Trip Delay
11
L1OverCurrenTrip
L1 Current was over L1 Overcurrent Level longer than Trip Delay
12
L2OverCurrenTrip
L2 Current was over L2 Overcurrent Level longer than Trip Delay
13
L3OverCurrenTrip
L3 Current was over L3 Overcurrent Level longer than Trip Delay
14
L1LineLossTrip
L1 Current Lost for longer than the L1 Loss Trip Delay
15
L2LineLossTrip
L2 Current Lost for longer than the L2 Loss Trip Delay
16
L3LineLossTrip
L3 Current Lost for longer than the L3 Loss Trip Delay
17
UnderVoltageTrip
Line to Line Under-Voltage condition detected
18
OverVoltageTrip
Line to Line Over-Voltage condition detected
19
VoltageUnbalTrip
Phase to phase voltage imbalance detected
20
PhaseRotationTrp
The unit detects the supply voltage phases are rotated
21
UnderFreqTrip
Line voltage frequency is below trip level
22
OverFreqTrip
Line voltage frequency has exceeded trip level
23
Fault23
24
Fault24
25
Fault25
26
Fault26
27
Fault27
28
Fault28
29
Fault29
30
Fault30
31
Fault31
32
Fault32
33
UnderKWTrip
Total Real Power(kW)is below trip level
34
OverKWTrip
Total Real Power(kW)has exceeded trip level
35
UnderKVARConTrip
Under Total Reactive Power Consumed (+kVAR) condition detected
36
OverKVARConTrip
Over Total Reactive Power Consumed (+kVAR) condition detected
37
UnderKVARGenTrip
Under Total Reactive Power Generated (-kVAR) condition detected
38
OverKVARGenTrip
Over Total Reactive Power Generated (-kVAR) condition detected
39
UnderKVATrip
Total Apparent Power (VA or kVA or MVA) is below trip level
40
OverKVATrip
Total Apparent Power (VA or kVA or MVA) exceeded trip level
41
UnderPFLagTrip
Under Total Power Factor Lagging (-PF) condition detected
42
OverPFLagTrip
Over Total Power Factor Lagging (-PF) condition detected
43
UnderPFLeadTrip
Under Total Power Factor Leading (+PF) condition detected
44
OverPFLeadTrip
Over Total Power Factor Leading (+PF) condition detected
45
Fault45
46
Fault46
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......