Chapter 4
System Operation and Configuration
•
Total Power Factor
•
User-defined Value
Table 69 - Analog Output Selection Type
Update Rate
Analog Input Channels
The performance for the input channels of the E300 Analog I/O Expansion
Module is dependent on the filter setting for each channel. The total scan time
for the input channels of the module is determined by adding the conversion time
for all enabled input channels.
Table 70 - Analog Input Channel Conversion Time
Example:
•
Channel 00 is configured for a 3-wire RTD and 4 Hz filter (conversion
time = 1024 ms).
•
Channel 01 is configured for 17Hz voltage (conversion time = 153 ms).
•
Channel 02 is configured for 62Hz current (conversion time = 65 ms).
Output Selection
Low Range
High Range
Average % FLA
0%
100%
Scaled Average % FLA
0%
200%
% TCU
0%
100%
Ground Fault Current
Internal, 0.50…5.00 A
0.50 A
5.00 A
External, 0.02…0.10 A
0.02 A
0.10 A
External, 0.10…0.50 A
0.10 A
0.50 A
External, 0.20…1.00 A
0.20 A
1.00 A
External, 1.00…5.00 A
1.00 A
5.00 A
Current Imbalance
0%
100%
Average L-L Voltage
0V
(PT Primary) V
Voltage Imbalance
0%
100%
Total kW
0 kW
(FLA1 x PT Primary x 1.732) V
Total kVAR
5.25V DC
(FLA1 x PT Primary x 1.732) V
Total kVA
5.00V DC
(FLA1 x PT Primary x 1.732) V
Total Power Factor
-50% (Lagging)
+50% (Leading)
User-defined Value
-32768
32767
Input Type
Filter Frequency
Conversion Time
Current, Voltage,
2-Wire RTD, Resistance
17 Hz
153 ms
4 Hz
512 ms
62 Hz
65 ms
470 Hz
37 ms
3-Wire RTD
17 Hz
306 ms
4 Hz
1024 ms
62 Hz
130 ms
470 Hz
74 ms
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......