Rockwell Automation Publication 193-UM015D-EN-P - February 2015
213
Protective Trip and Warning Functions
Chapter 6
Reactive Power (kVAR) Protection
The E300 Electronic Overload Relay has the capability to help protect against
reactive power (kVAR) for specific applications that require the monitoring of
both voltage and current. You can help protect or issue a warning if the reactive
power (kVAR) of an electric motor is either too high or too low.
Under kVAR Consumed Inhibit Time
Under kVAR Consumed Inhibit Time (Parameter 386) allows you to inhibit an
under reactive power (kVAR) consumed trip and warning from occurring during
the motor starting sequence. It is adjustable from 0…250 seconds.
Table 260 - Under kVAR Consumed Inhibit Time (Parameter 386)
Over kVAR Consumed Inhibit Time
Over kVAR Consumed Inhibit Time (Parameter 390) allows you to inhibit an
over reactive power (kVAR) consumed trip and warning from occurring during
the motor starting sequence. It is adjustable from 0…250 seconds.
Table 261 - Over kVAR Consumed Inhibit Time (Parameter 390)
IMPORTANT
The Over kW Warning function does not include a time delay feature. Once the
Over kW Inhibit Time has expired, the Over kW Warning indication is
instantaneous.
Default Value
10
Minimum Value
0
Maximum Value
250
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
Seconds
Default Value
10
Minimum Value
0
Maximum Value
250
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
Seconds
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......