Chapter 6
Protective Trip and Warning Functions
Table 250 - Power Trip Status (Parameter 6)
Table 251 - Power Warning Status (Parameter 12)
Real Power (kW) Protection
The E300 Electronic Overload Relay has the capability to help protect against
real power (kW) for specific applications that require the monitoring of both
voltage and current. You can help protect or issue a warning ifthe real power
(kW) consumption of an electric motor is either too high or too low.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Under kW Trip
X
Over kW Trip
X
Under kVAR Consumed Trip
X
Over kVAR Consumed Trip
X
Under kVAR Generated Trip
X
Over kVAR Generated Trip
X
Under kVA Trip
X
Over kVA Trip
X
Under PF Lagging Trip
X
Over PF Lagging Trip
X
Under PF Leading Trip
X
Over PF Leading Trip
Reserved
Reserved
Reserved
Reserved
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Under kW Warning
X
Over kW Warning
X
Under kVAR Consumed Warning
X
Over kVAR Consumed Warning
X
Under kVAR Generated Warning
X
Over kVAR Generated Warning
X
Under kVA Warning
X
Over kVA Warning
X
Under PF Lagging Warning
X
Over PF Lagging Warning
X
Under PF Leading Warning
X
Over PF Leading Warning
Reserved
Reserved
Reserved
Reserved
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......