Rockwell Automation Publication 193-UM015D-EN-P - February 2015
495
Parameter List
Appendix
B
Analog3 Setup
498
OutAnMod2PFltAct
C.Analog2.Ch00OutputProtectionFaultMode_0
C.Analog2.Ch00OutputProtectionFaultMode_1
Analog Module 2
Output action on a
protection fault
USINT
1
1
0= Ignore
1= Maximum
2= Minimum
3= HoldLastState
0
499
InAnMod3Ch00Type
C.Analog3.Ch00InputRangeType_0
C.Analog3.Ch00InputRangeType_1
C.Analog3.Ch00InputRangeType_2
C.Analog3.Ch00InputRangeType_3
C.Analog3.Ch00InputRangeType_4
Assignment for
Analog Module 3
Input Channel 00
function
USINT
1
1
0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
500
InAMod3Ch0Format
C.Analog3.Ch00InputFormat_0
C.Analog3.Ch00InputFormat_1
C.Analog3.Ch00InputFormat_2
Assignment for
Analog Module 3
Input Channel 00
Data Format
USINT
1
1
0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
501
InAMod3C0TmpUnit
C.Analog3.Ch00InputTempMode
Assignment for
Analog Module 3
Input Channel 00
Temperature Units
USINT
1
1
0=DegreesC
1=DegreesF
0
502
InAMod3C0FiltFrq
C.Analog3.Ch00InputFilter_0
C.Analog3.Ch00InputFilter_1
C.Analog3.Ch00InputFilter_2
Assignment for
Analog Module 3
Input Channel 00
Filter Freq
USINT
1
1
0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
503
InAMod3C0OpCktSt C.Analog3.Ch00InputOpenWire_0
C.Analog3.Ch00InputOpenWire_1
Indicates Analog
Module 3 Input
Channel 00 Open
Circuit State
USINT
1
1
0=Upscale
1=Downscale
2=Zero
0
504
InAnMod3Ch0RTDEn
C.Analog3.Ch00InputTwoWireRTD
Enable Analog
Module 3 Input
Channel 00 to
function with RTD
BOOL
1
1
0=3-wire
1=2-wire
0
505
InAMod3C0TripDly
C.Analog3.Ch00InputTripDelay
Analog Module 3
Input Channel 00
Trip Delay
USINT
1
10
0
250
10
Second
s
506
InAMod3C0TripLvl
C.Analog3.Ch00InputTripLimit
Level (in selected
Units) where
Analog Input
generates a trip
UINT
2
1
-32768
32767
0
507
InAMod3C0WarnLvl
C.Analog3.Ch00InputWarnLimit
Level (in selected
Units) where
Analog Input
generates a
warning
UINT
2
1
-32768
32767
0
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......