46
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 2
Installation and Wiring
Table 9 - Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C IEC
contactors that are protected by Bul. 140U-D circuit breakers
Table 10 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with
Bul. 500 line NEMA contactors that are protected by fuses
Fuse Coordination
The following tables list Type I and Type II Fuse Coordination when used with
Bulletin 100-C and 100-D and Bulletin 500 NEMA Size 00… 2 Contactors.
Overload Relay with
Sensing Module Cat. No.
Contactor Cat. No.
Max. Starter FLC[A]
Max. Available Fault
Current [A]
Max. Voltage [V]
Max. Circuit Breaker
Cat. No. 140U-D6D3-
193-ESM-___-30A-C23
100-C09
9
65,000
480Y/277V
C30 (30 A)
100-C12
12
100-C16
16
100-C23
23
193-ESM-___-30A-C23
100-C09
9
35,000
600Y/347V
C30 (30 A)
100-C12
12
100-C16
16
100-C23
23
193-ESM-___-30A-C23
100-C09
9
5,000
600Y/347V
C30 (30 A)
100-C12
12
100-C16
16
100-C23
23
Overload Relay with Sensing Module
Cat. No.
Contactor Size
Max. Starter FLC [A]
Max. Available Fault
Current [A]
Max. Voltage
[V]
Max. UL Fuse [A]
R
J
592-ESM-___-30A-S2
00
9
100,000
600
—
20
592-ESM-___-30A-S2
0
18
240
30
30
600
30
30
592-ESM-___-30A-S2
1
27
240
60
100
600
30
50
592-ESM-___-60A-S2
2
45
240
100
200
600
60
100
592-ESM-___-100A-S3
3
90
240
200
350
600
100
200
ATTENTION:
Select the motor branch circuit protection that complies with the
NEC and any other governing regional or local codes.
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......