Rockwell Automation Publication 193-UM015D-EN-P - February 2015
177
Protective Trip and Warning Functions
Chapter 6
When the L2 Over Current Warning conditions are satisfied, the:
•
TRIP/WARN LED flashes a yellow 13-short blink pattern
•
Bit 12 in Current Warning Status (Parameter 10) sets to 1
•
Bit 1 in Device Status 0 (Parameter 20) sets to 1
•
Any relay outputs configured as a Warning Alarm closes
L3 Over Current Warning Level
L3 Over Current Warning Level (Parameter 284) allows you to define the current
at which the E300 Electronic Overload Relay indicates a L3 Over Current
warning. It is user-adjustable from 10…100% for the FLA Setting (Parameter
171).
Table 216 - L3 Over Current Warning Level (Parameter 284)
Line Loss Protection
For non-motor applications when the measured current is 0 amps a specific
phase, this may indicate an electrical malfunction such as bad resistive heater
element or non-operating incandescent light bulb. Such conditions may not
harm the power system, but it can lead to loss of production or certification
noncompliance.
The E300 Electronic Overload Relay can monitor for a current-based line loss
per phase with its Line Loss Trip and Warning function to detect for a rapid line
loss in a specific phase to minimize damage and loss of production.
Line Loss Inhibit Time
Line Loss Inhibit Time (Parameter 285) allows you to inhibit an L1, L2, and L3
Line Loss trip and warning from occurring during a load starting sequence. It is
adjustable from 0…250 seconds.
Default Value
90
Minimum Value
10
Maximum Value
100
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
%FLA
IMPORTANT
The L3 Over Current Warning function does not include a time delay feature.
Once the Over Current Inhibit Timer has expired, the L3 Over Current Warning
indication is instantaneous.
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......