Rockwell Automation Publication 193-UM015D-EN-P - February 2015
333
Metering and Diagnostics
Chapter 8
set to 0. When Single or Three Phase (Parameter 176) is set to
Single Phase
, L3
Real Power is set to 0.
Table 415 - L3 Real Power (Parameter 66)
Total Real Power
Total Real Power (Parameter 67) reports the total real power of the monitored
power conductors in kW or MW depending on the configuration value for
Power Scale (Parameter 377). When Single or Three Phase (Parameter 176) is set
to
Three Phase
, Total Real Power is calculated as follows:
Total Real Power = (L1 Real Power + L2 Real Power + L3 Real Power)
When Single or Three Phase (Parameter 176) is set to
Single Phase
, Total Real
Power is calculated as follows:
Total Real Power = (L1 Real Power + L2 Real Power)
Table 416 - Total Real Power (Parameter 67)
L1 Reactive Power
L1 Reactive Power (Parameter 68) reports the reactive power for line 1 in kVAR
or MVAR depending on the configuration value for Power Scale (Parameter
377). When Voltage Mode (Parameter 352) is set to any
Delta
base setting, L1
Reactive Power is set to 0.
Default Value
0.000
Minimum Value
-2000000.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kW or MW
Default Value
0.000
Minimum Value
-2000000.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kW or MW
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......