Protective Trip and Warning Functions
Chapter 6
Figure 46 - Time-Current Characteristics for Trip Classes 5, 10, 20, and 30
For trip class time-current characteristics other than 5, 10, 20, or 30, scale the
Class 10 trip time according to the following table:
Table 165 - Time-Current Characteristic Scaling Factors
Automatic/Manual Reset
Overload Reset Mode (Parameter 173) allows you to select the reset mode for the
E300 Electronic Overload Relay after an overload or thermistor (PTC) trip. If an
overload trip occurs and automatic reset mode is selected, the E300 Electronic
Overload Relay automatically resets when the value stored in % Thermal
Capacity Utilized (Parameter 1) falls below the value stored in Overload Reset
Level (Parameter 174). If manual reset mode is selected, the E300 Overload
Trip Class
Trip Class 10
Multiplier
Trip Class
Trip Class 10
Multiplier
Trip Class
Trip Class 10
Multiplier
5
0.5
14
1.4
23
2.3
6
0.6
15
1.5
24
2.4
7
0.7
16
1.6
25
2.5
8
0.8
17
1.7
26
2.6
9
0.9
18
1.8
27
2.7
10
1.0
19
1.9
28
2.8
11
1.1
20
2.0
29
2.9
12
1.2
21
2.1
30
3.0
13
1.3
22
2.2
1
10
100
1000
100%
1000%
Time (seconds)
Trip Class 5
Current (% FLA)
Trip Class 30
1
10
100
1000
10000
100%
1000%
Current (% FLA)
Time (seconds)
1
10
100
1000
10000
100%
1000%
Trip Class 20
Time (seconds)
Current (% FLA)
1
10
100
1000
100%
1000%
Time (seconds)
Trip Class 10
Current (% FLA)
Cold Trip
Hot Trip
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......