220
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 6
Protective Trip and Warning Functions
Under kVAR Generated Trip
The E300 Electronic Overload Relay trips with an Under kVAR Generated
indication if:
•
No trip currently exists
•
Under kVAR Generated Trip is enabled
•
Current is present
•
Voltage is present
•
Under kVAR Generated Inhibit Time has expired
•
The total reactive power (kVAR) generated is less than the Under
•
kVAR Generated Trip Level for a time period greater than the Under
kVAR Generated Trip Delay.
If the E300 Electronic Overload Relay trips on an under reactive power (kVAR)
generated, the:
•
TRIP/WARN LED status indicator flashes a red 2-long / 5-short blink
pattern
•
Bit 4 in Power Trip Status (Parameter 6) sets to 1
•
Bit 0 in Device Status 0 (Parameter 20) sets to 1
•
Any relay outputs configured as a Trip Relay open
•
Any relay outputs configured as a Control Relay open
•
Any relay outputs configured as a Trip Alarm close
•
Any relay outputs configured as a Normal Relay are placed in their
Protection Fault state (if so programmed)
IMPORTANT
The Over kVAR Consumed Warning function does not include a time delay
feature. Once the Over kVAR Consumed Inhibit Time has expired, the Over kVAR
Consumed Warning indication is instantaneous.
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......