Rockwell Automation Publication 193-UM015D-EN-P - February 2015
79
System Operation and Configuration
Chapter 4
Input Pt05 Assignment (Parameter 201)
Input Pt05 Assignment (Parameter 201) allows you to assign this digital input
for the following functions:
Table 44 - Input Pt05 Assignment (Parameter 201)
Value
Assignment
Description
0
Normal
Function as a digital input
1
Trip Reset
Reset the E300 when it is in a tripped state
2
Remote Trip
Force the E300 to go into a tripped state
3
Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
4
Force Snapshot
Force the E300 to update its Snapshot log
5
Emergency Start
Issue an Emergency Start command
6
Test Mode
Enable Test Mode monitoring
7
L1 Line Loss Arm
Activate L1 Line Loss Protection
8
L2 Line Loss Arm
Activate L2 Line Loss Protection
9
L3 Line Loss Arm
Activate L3 Line Loss Protection
10
L1 L2 Line Loss Arm
Activate L1 and L2 Line Loss Protection
11
L2 L3 Line Loss Arm
Activate L2 and L3 Line Loss Protection
12
L1 L3 Line Loss Arm
Activate L1 and L3 Line Loss Protection
13
L1 L2 L3 Line Loss Arm
Activate L1, L2, and L3 Line Loss Protection
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......