96
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 4
System Operation and Configuration
Table 72 - Analog Module 1 – Input Channel 00 Format (Parameter 438)
Analog Module 1 – Input Channel 00 Temperature Unit
Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439)
defines the temperate unit for RTD sensor readings.
Table 73 - Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439)
Analog Module 1 – Input Channel 00 Filter Frequency
Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440) defines
update rate for the analog module’s input channels.
Table 74 - Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440)
Analog Module 1 – Input Channel 00 Open Circuit State
Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441)
defines what the input channel reports when the input channel has an open
circuit. Open circuit detection is always enabled for this input channel.
Table 75 - Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441)
Analog Module 1 – Input Channel 00 RTD Type Enable
Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442)
defines the type of RTD to monitor when the input channel type is configured to
scan an RTD sensor.
Value
Assignment
Description
0
EngUnits
Engineering Units (mA, V, °C, °F, or Ω)
1
EngUnitsTimes10
Engineering Units x 10 (mA, V, °C, °F, or Ω)
2
RawProportional
Raw / Proportional (-32768…+32767)
3
ScaledForPID
Scaled for PID (0…16383)
Value
Assignment
Description
0
DegreesC
Report RTD Temperature Data in °C
1
DegreesF
Report RTD Temperature Data in °F
Value
Assignment
Description
0
17 Hz
Analog to Digital Conversion Update Frequency of 17 Hz
1
4 Hz
Analog to Digital Conversion Update Frequency of 4 Hz
2
62 Hz
Analog to Digital Conversion Update Frequency of 62 Hz
3
470 Hz
Analog to Digital Conversion Update Frequency of 470Hz
Value
Assignment
Description
0
Upscale
Reports the high limit of the input channel type
1
Downscale
Reports the low limit of the input channel type
2
Zero
Reports zero
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......