456
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Appendix A
Specifications
Environmental Specifications
➊
Current ratings must be derated at altitudes greater than 2000 m
➋
Temperature rating based on 120V AC control module with 1 A going through relays 0, 1, and 2.
➌
Temperature rating based on 24V DC control module with four digital inputs active and 0.2 A going through
relays 0, 1, and 2.
➍
Temperature rating based on 120V AC or 240V AC control module with 5A going through relays 0, 1, and 2.
NOTE:
The E300 Electronic Overload Relay expansion power supplies (Cat.
Nos. 193-EXP-PS-AC and 193-EXP-PS-DC) surrounding air temperature must
not exceed 55 °C (131 °F).
Table 515 - Temperature Derating
Table 513 - Expansion Power Supply Modules
Expansion Power Supply Modules
193-EXP-PS-AC
Rated Operational Voltage (U
e
):
100…250V AC
Rated Insulation Voltage (U
i
):
2640Vrms for 1s
Rated Impulse Withstand Voltage (U
imp
):
4 kV
Conditional Short Circuit Current:
N/A
Protection Against Short Circuits:
N/A
Utilization Category:
N/A
Pollution Degree:
3
Table 514 - Environmental Specifications
Ambient Temperature
Storage
Operating
(Open)
(Enclosed)
–40…+85
C (–40…+185
F)
–20…+55
C (–4…+131
F)
➋➌
–20…+40
C (–4…+104
F)
➌➍
Humidity
Operating
Damp Heat – Steady State (per IEC 68-2-3)
Damp Heat – Cyclic (per IEC 68-2-30)
5…95% Non-condensing
92% r.h., 40
C (104
F), 56 days
93% r.h., 25
C/40
C (77
F/104
F), 21 Cycles
Cooling Method
Natural Convection
Vibration (per IEC 68-2-6)
2.5G operating, 5 G non-operating
Shock (per IEC 68-2-27)
30 G
Maximum Altitude
2000 m
➊
Pollution Environment
Pollution Degree 3
Terminal Marking
EN 50012
Degree of Protection
IP20
Control Module
Voltage
Relay 0
Current
Relay 1
Current
Relay 2
Current
Number of
Digital Inputs
Active
Operating Temperature
Range
Open Application
120/240V AC
1.0 A
1.0 A
1.0 A
4
-20…+55 °C (-4…+131 °F)
5.0 A
1.0 A
1.0 A
4
-20…+50 °C (-4…+122 °F)
24V DC
0.2 A
0.2 A
0.2 A
4
-20…+55 °C (-4…+131 °F)
0.2 A
0.2 A
0.2 A
6
-20…+50 °C (-4…+122 °F)
5.0 A
1.0 A
1.0 A
6
-20…+30 °C (-4…+86 °F)
Enclosed
Application
120/240V AC
5.0 A
5.0 A
5.0 A
4
-20…+40 °C (-4…+104 °F)
24V DC
0.2 A
0.2 A
0.2 A
4
-20…+40 °C (-4…+104 °F)
5.0 A
1.0 A
1.0 A
6
-20…+30 °C (-4…+86 °F)
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......