100
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 4
System Operation and Configuration
Analog Module 1 – Input Channel 02 Filter Frequency
Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458) defines
update rate for the analog module’s input channels.
Table 86 - Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458)
Analog Module 1 – Input Channel 02 Open Circuit State
Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459)
defines what the input channel reports when the input channel has an open
circuit. Open circuit detection is always enabled for this input channel.
Table 87 - Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459)
Analog Module 1 – Input Channel 02 RTD Type Enable
Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460)
defines the type of RTD to monitor when the input channel type is configured to
scan an RTD sensor.
Table 88 - Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460)
Analog
Module
1
–
Output
Channel
00
Type
Analog Module 1 – Output Channel 00 Type (Parameter 464) defines the type
of analog signal that Output Channel 00 of Analog Module 1 will be providing.
Table 89 - Analog Module 1 – Output Channel 00 Type (Parameter 464)
Value
Assignment
Description
0
17 Hz
Analog to Digital Conversion Update Frequency of 17 Hz
1
4 Hz
Analog to Digital Conversion Update Frequency of 4 Hz
2
62 Hz
Analog to Digital Conversion Update Frequency of 62 Hz
3
470 Hz
Analog to Digital Conversion Update Frequency of 470Hz
Value
Assignment
Description
0
Upscale
Reports the high limit of the input channel type
1
Downscale
Reports the low limit of the input channel type
2
Zero
Reports zero
Value
Assignment
Description
0
3-Wire
Scan a 3-wire RTD sensor
1
2-Wire
Scan a 2-wire RTD sensor
Value
Assignment
Description
0
Disabled
Disable the analog input
1
4To20mA
Provide an analog current signal from 4…20 mA
2
0To20mA
Provide an analog current signal from 0…20 mA
3
0To10Volts
Provide an analog voltage signal from 0…10 V DC
4
1To5Volts
Provide an analog voltage signal from 1…5 V DC
5
0To5Volts
Provide an analog voltage signal from 0…5 V DC
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......