Chapter 4
System Operation and Configuration
Table 155 - Analog Module 4 – Output Channel 00 Type (Parameter 557)
Analog Module 4 – Output Channel 00 Selection
Analog Module 4 – Output Channel 00 Selection (Parameter 558) defines the
E300 Electronic Overload Relay parameter that Output Channel 00 will be
representing.
Table 156 - Analog Module 4 – Output Channel 00 Selection (Parameter 558)
Analog Module 4 – Output Channel 00 Expansion Bus Fault Action
Analog Module 4 – Output Channel 00 Expansion Bus Fault Action (Parameter
559) defines the value that the E300 Analog I/O Expansion Module Output
Channel 00 provides when there is an E300 Expansion Bus fault.
Table 157 - Analog Module 4 – Output Channel 00 Expansion Bus Fault Action (Parameter 559)
Analog Module 4 – Output Channel 00 Protection Fault Action
Analog Module 4 – Output Channel 00 Expansion Bus Fault Action (Parameter
560) defines the value that the E300 Analog I/O Expansion Module Output
Channel 00 provides when the E300 is in a tripped state.
Value
Assignment
Description
0
Disabled
Disable the analog input
1
4To20mA
Provide an analog current signal from 4…20 mA
2
0To20mA
Provide an analog current signal from 0…20 mA
3
0To10Volts
Provide an analog voltage signal from 0…10 V DC
4
1To5Volts
Provide an analog voltage signal from 1…5 V DC
5
0To5Volts
Provide an analog voltage signal from 0…5 V DC
Value
Assignment
Description
0
AveragePCTFLA
Average %FLA (0…100%)
1
ScaledAvgPctFLA
Scaled Average %FLA (0…200%)
2
PercentTCU
%TCU (0…100%)
3
GFCurrent
Ground Fault Current (Ground Fault Type Range)
4
CurrentImbalance
Current Imbalance (0…100%)
5
AvgLLVoltage
Average L-L Voltage (0…PT Primary)
6
VoltLLImbalance
Voltage Imbalance (0…100%)
7
TotalkW
Total kW (0…FLA x PT Primary x 1.732)
8
TotalkVA
Total kVA (0…FLA x PT Primary x 1.732)
9
Total kVAR
Total kVAR (0…FLA x PT Primary x 1.732)
10
TotalPF
Total Power Factor (-50% L50% Leading)
11
UserDLXData
User-defined Value (-32768…32767)
Value
Assignment
Description
0
Zero
Provide an analog signal of zero
1
Maximum
Provide an analog signal equal to the high limit
2
Minimum
Provide an analog signal equal to the low limit
3
HoldLastState
Provide the last known analog signal
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......