Chapter 4
System Operation and Configuration
Analog Module 2 – Output Channel 00 Selection
Analog Module 2 – Output Channel 00 Selection (Parameter 496) defines the
E300 Electronic Overload Relay parameter that Output Channel 00 will be
representing.
Table 112 - Analog Module 2 – Output Channel 00 Selection (Parameter 496)
Analog Module 2 – Output Channel 00 Expansion Bus Fault Action
Analog Module 2 – Output Channel 00 Expansion Bus Fault Action (Parameter
497) defines the value that the E300 Analog I/O Expansion Module Output
Channel 00 provides when there is an E300 Expansion Bus fault.
Table 113 - Analog Module 2 – Output Channel 00 Expansion Bus Fault Action (Parameter 497)
Analog Module 2 – Output Channel 00 Protection Fault Action
Analog Module 2 – Output Channel 00 Expansion Bus Fault Action (Parameter
498) defines the value that the E300 Analog I/O Expansion Module Output
Channel 00 provides when the E300 is in a tripped state.
Table 114 - Analog Module 2 – Output Channel 00 Protection Fault Action (Parameter 498)
Value
Assignment
Description
0
AveragePCTFLA
Average %FLA (0…100%)
1
ScaledAvgPctFLA
Scaled Average %FLA (0…200%)
2
PercentTCU
%TCU (0…100%)
3
GFCurrent
Ground Fault Current (Ground Fault Type Range)
4
CurrentImbalance
Current Imbalance (0…100%)
5
AvgLLVoltage
Average L-L Voltage (0… PT Primary)
6
VoltLLImbalance
Voltage Imbalance (0… 100%)
7
TotalkW
Total kW (0…FLA x PT Primary x 1.732)
8
TotalkVA
Total kVA (0…FLA x PT Primary x 1.732)
9
Total kVAR
Total kVAR (0…FLA x PT Primary x 1.732)
10
TotalPF
Total Power Factor (-50% L50% Leading)
11
UserDLXData
User-defined Value (-32768… 32767)
Value
Assignment
Description
0
Zero
Provide an analog signal of zero
1
Maximum
Provide an analog signal equal to the high limit
2
Minimum
Provide an analog signal equal to the low limit
3
HoldLastState
Provide the last known analog signal
Value
Assignment
Description
0
Ignore
Continue providing the appropriate analog signal
1
Maximum
Provide an analog signal equal to the high limit
2
Minimum
Provide an analog signal equal to the low limit
3
HoldLastState
Provide the analog signal at the time of the fault
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......