background image

Power Supply :

 No Power Supply to be given separetely

Tripping Parameters :

 Under voltage

                        Over voltage
                        Phase asymmetry
                        Phase sequence
                        Phase loss

Output:

 1 Relay 1C/O ,5A 230V AC Resistive load

Input Voltage :

 280 to 520V AC ( L- L ) 3Ø -3W

Voltage Protection Relay

   VPR-22U

UNDER VOLTAGE 
        KNOB

 

OVER VOLTAGE 
      KNOB

 

FAULT INDICATION LED

for under voltage, over voltage,
phase sequence, phase asymmetry
& phase loss

MAIN LED

 

for visualisation of power 

supply status 

Rated Voltage :

 415V AC ( L- L ) 

PIANO SWITCH 

for time range selection &
Power ON & Trip Delay Time selection

ON 

OFF

Switch 

Settings

1  2  3  4 

       Switch-1 & 2 for 
       Power ON Delay 
       time selection
                 
         

ON
ON
OFF
OFF

15 Sec
10 Sec

5 Sec
2 Sec

SW 1
   

Range

ON
OFF
ON
OFF

SW 2
   

ON
ON
OFF
OFF

15 Sec
10 Sec

5 Sec
2 Sec

SW 3
   

Range

ON
OFF
ON
OFF

SW 4
   

       Switch-3 & 4 for 
       Trip Delay 
       time selection
                 
         

 
RED: 

phase loss

Blinking Red: phase asymmetry
Yellow: 

phase sequence

OFF: Healthy

Reviews: