Rockwell Automation Publication 193-UM015D-EN-P - February 2015
63
Chapter
4
System Operation and Configuration
Introduction
This chapter provides instructions for operating and configuring an E300
Electronic Overload Relay system. Settings for Device Modes, Option Match,
Security Policy, I/O Assignments, Expansion Bus Fault, Emergency Start, and an
introduction to Operating Modes are included in this chapter.
Device Modes
The E300 Electronic Overload Relay has five device modes to validate
configuration of the device and limit when you can configure the E300
Electronic Overload Relay, perform a firmware update, and issue commands.
•
Administration Mode
•
Operation Mode
•
Run Mode
•
Test Mode
•
Invalid Configuration Mode
Administration Mode
Administration Mode is a maintenance mode for the E300 Electronic Overload
Relay, which allows you to configure parameters, modify security policies, enable
web servers (see
to enable the EtherNet/IP web server), perform
firmware updates, and issue commands.
Follow these steps to enter into Administration Mode:
1.
Set the rotary dials on the E300 Communication Module to the following
values
–
For EtherNet/IP set the rotary dials to 0-0-0
–
For DeviceNet set the rotary dials to 7-7
2.
Cycle power on the E300 Electronic Overload Relay
After commissioning activities and maintenance tasks are completed, return the
E300 Electronic Overload Relay back to Operation or Run Mode by setting the
rotary dials of the E300 communication module back to its previous positions
and cycle power.
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......