Chapter 4: Connecting External Equipment (Optional)
65
Make sure that the U-shaped sheet metal adjacent to the male
DIN connector is inserted into the rear slot of the master strip.
Screw up the U-shaped sheet metal to reinforce the connection.
2.
Connect another 8U slave strip to the one being attached to the
master strip in the same manner as Step 1.
3.
Repeat the above step to connect more slave strip. The length of the
asset strip assembly can be up to 64U.
The final slave strip can be 8U or 5U, depending on the actual
height of your rack.
Connect the "ending" asset strip as the final one in the assembly.
4.
Vertically attach the asset strip assembly to the rack, next to the IT
equipment, making each tag port horizontally align with a rack unit.
5.
The asset strips are automatically attracted to the rack because of
magnetic stripes on the back.
Note: The asset strip is implemented with a tilt sensor so it can be
mounted upside down.